UPSDRVCTL(8)		    Network UPS Tools (NUT)		  UPSDRVCTL(8)

NAME
       upsdrvctl - UPS driver controller

SYNOPSIS
       upsdrvctl -h

       upsdrvctl [OPTIONS] {start | stop | shutdown} [ups]

DESCRIPTION
       upsdrvctl  provides  a uniform interface for controlling your UPS driv‐
       ers.  You should use upsdrvctl instead of direct calls to  the  drivers
       whenever possible.

       When  used  properly,  upsdrvctl	 lets  you  maintain identical startup
       scripts across multiple systems with different UPS configurations.

OPTIONS
       -h     Display the help message.

       -r directory
	      If starting a driver, this value will  direct  it	 to  chroot(2)
	      into directory.  This can be useful when securing systems.

	      This may be set in the ups.conf with "chroot" in the global sec‐
	      tion.

       -t     Enable testing mode.  This also  enables	debug  mode.   Testing
	      mode  makes upsdrvctl display the actions it would execute with‐
	      out actually doing them.	Use this to test out  your  configura‐
	      tion  without actually doing anything to your UPS drivers.  This
	      may be helpful when defining the	'sdorder'  directive  in  your
	      ups.conf(5).

       -u username
	      If  starting a driver, this value will direct it to setuid(2) to
	      the user id associated with username.

	      If the driver is started as root without specifying this	value,
	      it  will	use  the  username  that was compiled into the binary.
	      This defaults to "nobody", and is far from ideal.

	      This may be set in ups.conf with "user" in the global section.

       -D     Raise the debug level.  Use this multiple times  for  additional
	      details.

COMMANDS
       upsdrvctl  supports  three  commands  ‐ start, stop and shutdown.  They
       take an optional argument which is a UPS name from ups.conf(5).	 With‐
       out  that argument, they operate on every UPS that is currently config‐
       ured.

       start  Start the UPS driver(s).

       stop   Stop the UPS driver(s).

       shutdown
	      Command the UPS driver(s) to run their shutdown sequence.	 Driv‐
	      ers   are	 stopped  according  to	 their	sdorder	 value	‐  see
	      ups.conf(5).

	      WARNING: this will probably power off your computers,  so	 don't
	      play around with this option.  Only use it when your systems are
	      prepared to lose power.

ENVIRONMENT VARIABLES
       NUT_CONFPATH is the path name of the directory that contains  ups.conf.
       If  this	 variable  is not set, upsdrvctl and the driver use a built‐in
       default, which is often /usr/local/ups/etc.

DIAGNOSTICS
       upsdrvctl will return a nonzero exit code if  it	 encounters  an	 error
       while  performing  the  desired	operation.  This will also happen if a
       driver takes longer than the maxstartdelay period to  enter  the	 back‐
       ground.

SEE ALSO
       nutupsdrv(8), upsd(8) ups.conf(5)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Sat Jan 31 2004			  UPSDRVCTL(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net