SAFENET(8)		    Network UPS Tools (NUT)		    SAFENET(8)

NAME
       safenet - Driver for SafeNet compatible UPS equipment

NOTE
       This  man  page	only  documents	 the hardware‐specific features of the
       safenet driver.	For information about the  core	 driver,  see  nutups‐
       drv(8).

SUPPORTED HARDWARE
       This  driver supports UPS equipment which can be controlled via SafeNet
       v1.0 for Windows (serial interface only).

EXTRA ARGUMENTS
       This  driver  supports  the  following	optional   settings   in   the
       ups.conf(5):

       manufacturer=value
	      Autodetection  of	 this  parameter  is  not possible yet (and it
	      probably never will be). Therefore,  this	 user  defined	string
	      accepts any name. The default is unknown.

       modelname=value
	      Like manufacturer above. The default is unknown.

       serialnumber=value
	      Like manufacturer above. The default is unknown.

       ondelay=value
	      Time  to wait before switching on the UPS (minutes). Defaults to
	      1 minute.

       offdelay=value
	      Time to wait before shutting down the UPS (seconds). Defaults to
	      30 seconds.

UPSCMD
       This driver supports some instant commands (see upscmd(8)):

       test.battery.start
	      Start UPS self test

       test.battery.stop
	      Cancel UPS self test

       test.failure.start
	      Start simulated power failure

       test.failure.stop
	      Cancel simulated power failure

       beeper.enable
	      Enable the UPS beeper

       beeper.mute
	      Temporarily mute the UPS beeper

       beeper.toggle
	      Toggle the UPS beeper

       shutdown.return
	      Turn  off	 the  load  and wait for the power to return. Uses the
	      timer defined by offdelay.

       shutdown.reboot
	      Turn off the load and return. Uses the timers defined by	offde‐
	      lay and ondelay.

KNOWN PROBLEMS
       If  you	run the shutdown.return command with mains present, the output
       may stay on or switch off and not back on  again.  The  shutdown.reboot
       command	will unconditionally switch on the load again (with or without
       mains present).

       If the driver is called with the	 '‐k'  option  (or  through  upsdrvctl
       shutdown) it tries to detect which command should be used in an attempt
       to stay off until mains is present again or to cycle the output if  the
       power returned in the mean time. This isn't bullet proof and you should
       be prepared that the power will either  not  be	shutdown  or  that  it
       doesn't return when the power comes back.

AUTHOR
       Arjen de Korte <adkorte‐guest at alioth.debian.org>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Mon Dec 29 2008			    SAFENET(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net