NUTDRV_QX(8) NUT Manual NUTDRV_QX(8)NAMEnutdrv_qx - Driver for Q* protocol serial and USB based UPS equipment
NOTE
This man page only documents the hardware-specific features of the
nutdrv_qx driver. For information about the core driver, see
nutupsdrv(8).
SUPPORTED HARDWARE
The nutdrv_qx driver is known to work with various UPSes from Blazer,
Energy Sistem, Fenton Technologies, General Electric, Mustek, Voltronic
Power (rebranded by many, many - have I said many? - others.. Long
story short: if your UPS came with a software called Viewpower, chances
are high that it works with this driver with one of the voltronic*
protocols or with the mecer one) and many others.
The NUT compatibility table lists all the known supported models. Keep
in mind, however, that other models not listed there may also be
supported, but haven’t been tested.
All devices with a serial interface and many with a USB interface are
supported.
EXTRA ARGUMENTS
You may need to override or provide defaults for some values, depending
on the make and model of your UPS.
The following are the ones that most likely will need changing (see
ups.conf(5)):
ondelay = value
Time to wait before switching on the UPS (seconds). This value is
truncated to units of 60 seconds.
Note that a value below 3 minutes, may cause earlier firmware
versions to not switch on automatically, so it defaults to 3
minutes (i.e. 180 seconds).
This option provides a default value for ups.delay.start that will
then be used by the driver in the automatic shutdown sequence (i.e.
calling the driver with the -k option, calling upsdrvctl(8) with
the shutdown option or when the FSD flag is set and upsmon(8)
enters its shutdown sequence): however you can change this value
‘on the fly’ for the actual session, only for the use with instant
commands, setting ups.delay.start with upsrw(8).
offdelay = value
Time to wait before shutting down the UPS (seconds). This value is
truncated to units of 6 seconds (less than 60 seconds) or 60
seconds (more than 60 seconds). Defaults to 30 seconds.
This option provides a default value for ups.delay.shutdown that
will then be used by the driver in the automatic shutdown sequence
(i.e. calling the driver with the -k option, calling upsdrvctl(8)
with the shutdown option or when the FSD flag is set and upsmon(8)
enters its shutdown sequence): however you can change this value
‘on the fly’ for the actual session, only for the use with instant
commands, setting ups.delay.shutdown with upsrw(8).
stayoff
If you set stayoff in ups.conf(5) when FSD arises the UPS will call
a shutdown.stayoff shutting down after ups.delay.shutdown seconds
and won’t return (see KNOWN PROBLEMS), otherwise (standard
behaviour) the UPS will call shutdown.return shutting down after
ups.delay.shutdown seconds and then turn on after ups.delay.start
seconds (if mains meanwhile returned).
protocol = string
Skip autodetection of the protocol to use and only use the one
specified. Supported values: bestups, mecer, megatec, megatec/old,
mustek, q1, voltronic, voltronic-qs, voltronic-qs-hex and zinto.
Note that if you end up using the q1 protocol, you may want to give
a try to the mecer, megatec and zinto ones setting the
novendor/norating flags (only one, or both).
pollfreq = value
Set polling frequency, in seconds, to reduce the data flow. Between
two polling requests the driver will do ‘quick polls’ dealing just
with ups.status. The default value is 30 (in seconds).
If your UPS doesn’t report either battery.charge or battery.runtime you
may want to add the following ones in order to have guesstimated
values:
default.battery.voltage.high = value
Maximum battery voltage that is reached after about 12 to 24 hours
charging. If you want the driver to report a guesstimated
battery.charge, you need to specify this (see BATTERY CHARGE).
default.battery.voltage.low = value
Minimum battery voltage just before the UPS automatically shuts
down. If you want the driver to report a guesstimated
battery.charge, you need to specify this (see BATTERY CHARGE).
default.battery.voltage.nominal = value,
override.battery.voltage.nominal = value
Some devices show a wrong nominal battery voltage (or none at all),
so you may need to override or set a default value.
override.battery.packs = value
Some devices report a part of the total battery voltage. For
instance, if battery.voltage.nominal is 24 V, but it reports a
battery.voltage of around 2 V, the number of battery.packs to
correct this reading would be 12. The driver will attempt to detect
this automatically, but if this fails somehow, you may want to
override this value.
runtimecal = value,value,value,value
Parameter used in the (optional) runtime estimation. This takes two
runtimes at different loads. Typically, this uses the runtime at
full load and the runtime at half load. For instance, if your UPS
has a rated runtime of 240 seconds at full load and 720 seconds at
half load, you would enter
runtimecal = 240,100,720,50
The first load should always be higher than the second. If you have
values available for loads other than 100 and 50 % respectively,
you can use those too, but keep them spaced apart as far as
reasonably possible. Just don’t get too close to no load
(prediction of runtime depends more on idle load for the battery
then).
chargetime = value
The time needed to fully recharge the battery after being fully
discharged. If not specified, the driver defaults to 43200 seconds
(12 hours). Only used if runtimecal is also specified.
idleload = value
Minimum battery load used by the driver to estimate the runtime. If
not specified, the driver defaults to 10%. Only used if runtimecal
is also specified.
BESTUPS, MECER, MEGATAEC, MEGATEC/OLD, MUSTEK, Q1, VOLTRONIC-QS,
VOLTRONIC-QS-HEX, ZINTO PROTOCOLS
ignoresab
Some UPSes incorrectly report the ‘Shutdown Active’ bit as always
on, consequently making the driver believe the UPS is nearing a
shutdown (and, as a result, ups.status always contains FSD... and
you know what this means). Setting this flag will make the driver
ignore the ‘Shutdown Active’ bit.
MECER, MEGATAEC, MEGATEC/OLD, MUSTEK, ZINTO PROTOCOLS
ondelay
The acceptable range is 0..599940 seconds.
offdelay
The acceptable range is 12..600 seconds.
norating
Some UPSes will lock up if you attempt to read rating information
from them. Setting this flag will make the driver skip this step.
novendor
Some UPSes will lock up if you attempt to read vendor information
from them. Setting this flag will make the driver skip this step.
BESTUPS PROTOCOL
ondelay
The acceptable range is 60..599940 seconds.
offdelay
The acceptable range is 12..5940 seconds.
pins_shutdown_mode = value
Set shutdown mode functionality of Pin 1 and Pin 7 on the UPS DB9
communication port (Per Best Power’s EPS-0059) to value [0..6].
Q1 PROTOCOL
ondelay
The acceptable range is 0..599940 seconds.
offdelay
The acceptable range is 12..600 seconds.
VOLTRONIC-QS, VOLTRONIC-QS-HEX PROTOCOLS
ondelay
The acceptable range is 60..599940 seconds.
offdelay
The acceptable range is 12..540 seconds.
VOLTRONIC PROTOCOL
The following options are supported only by the voltronic protocol. Not
all of them are available on all the UPSes supported by this protocol.
ondelay
The acceptable range is 0..599940 seconds.
offdelay
The acceptable range is 12..5940 seconds.
battery_number = value
Set number of batteries that make a pack to value [1..9]. This
setting will change the charge and runtime estimation reported by
the UPS.
output_phase_angle = value
Changes output phase angle to the provided value [000, 120, 180,
240]°.
UPS CAPABILITY SETTINGS
reset_to_default
Reset capability options and their voltage and frequency limits
to safe default values. (Doable only when the UPS is in Standby
Mode)
Note that setting this option will reset also ups.start.auto,
battery.protection, battery.energysave, ups.start.battery,
outlet.0.switchable, input.transfer.high, input.transfer.low,
input.frequency.high and input.frequency.low.
These UPSes can be fine-tuned to suit your needs enabling or
disabling the following options (the driver should tell you which
one the UPS is capable of on startup: the settable ones will be
reported either ar enabled or disabled in the logs):
alarm_control = string
Enable or disable alarm (BEEP!) [enabled/disabled]. Settable
also ‘on the fly’ with beeper.enable and beeper.disable instant
commands.
bypass_alarm = string
Enable or disable alarm (BEEP!) at Bypass Mode
[enabled/disabled].
battery_alarm = string
Enable or disable alarm (BEEP!) at Battery Mode
[enabled/disabled].
bypass_when_off = string
Enable or disable bypass when the UPS is Off
[enabled/disabled]. If enabled, AC will directly provide power
to connected devices when the UPS is off.
bypass_forbidding = string
Enable or disable Bypass Forbidding [enabled/disabled]. If
enabled, the UPS will not transfer to bypass mode under any
condition.
converter_mode = string
Enable or disable Converter Mode [enabled/disabled]. When input
frequency is within 40 Hz to 70 Hz, the UPS can be set at a
constant output frequency, 50 Hz or 60 Hz. The UPS will still
charge battery under this mode.
eco_mode = string
Enable or disable ECO Mode [enabled/disabled]. When input
voltage/frequency are within acceptable range, the UPS will
bypass voltage to output for energy saving. PFC and INVERTER
are still active at this mode. Settable also ‘on the fly’ with
bypass.start and bypass.stop instant commands.
advanced_eco_mode = string
Enable or disable Advanced ECO Mode [enabled/disabled]. When
input voltage/frequency are within acceptable range, the UPS
will bypass voltage to output for energy saving. PFC and
INVERTER are off at this mode.
battery_open_status_check = string
Enable or disable Battery Open Status Check [enabled/disabled].
If enabled, when the UPS is turned on, it will check if the
battery is connected or not.
site_fault_detection = string
Enable or disable site fault detection [enabled/disabled]. If
enabled, the UPS will beep when the input neutral and hot wires
are reversed.
constant_phase_angle = string
Enable or disable Constant Phase Angle Function (output and
input phase angles are not equal) [enabled/disabled].
limited_runtime_on_battery = string
Enable or disable limited runtime on battery mode
[enabled/disabled].
BYPASS MODE VOLTAGE/FREQUENCY LIMITS
Variables to fine-tune voltage and frequency limits for Bypass
mode. These limits are reset to safe default values by
reset_to_default.
If AC voltage and frequency are within acceptable range, Bypass
mode will be used (If the UPS is capable of and it’s enabled).
Since these values are device-specific, if your UPS support them,
you will get their settable limits printed in the logs on startup.
max_bypass_volt = value
Maximum voltage for Bypass Mode (V).
min_bypass_volt = value
Minimum voltage for Bypass Mode (V).
max_bypass_freq = value
Maximum frequency for Bypass Mode (Hz).
min_bypass_freq = value
Minimum frequency for Bypass Mode (Hz).
OPTIONS SPECIFIC FOR P31 UPSES
The following options are available only on P31 UPSes.
work_range_type = string
Device grid working range for P31 UPSes [Appliance/UPS].
TESTING
This protocol comes with a couple of functions that are not enabled
by default because of the lack of knowledge of some part of the
communication protocol used by these UPSes by your friendly
neighborhood developer. Since these functions are supposed to be
queries to the UPS for some kind of informations, they should not
make your UPS go boom. So if you are brave enough to risk your UPS
and attached devices' life to help the developers, this will be
very appreciated.. Do it at your own risk.
testing
If invoked the driver will exec also commands that still need
testing.
SERIAL INTERFACE ONLY
cablepower = string
By default the driver will set DTR and clear RTS (normal). If you
find that your UPS isn’t detected or the communication with the UPS
is unreliable, you may try if clear DTR and set RTS (reverse), set
DTR and RTS (both) or clear DTR and RTS (none) improves this
situation.
USB INTERFACE ONLY
port = string
You must set value to auto.
vendorid = regex, productid = regex, vendor = regex, product = regex,
serial = regex
Select a specific UPS, in case there is more than one connected via
USB. Each option specifies an extended regular expression (see
regex(7)) that must match the UPS’s entire vendor/product/serial
string (minus any surrounding whitespace), or the whole 4-digit
hexadecimal code for vendorid and productid. Try -DD for finding
out the strings to match.
Examples:
· -x vendor="Foo.Corporation.*"
· -x vendorid=051d* (APC)
· -x product=".*(Smart|Back)-?UPS.*"
bus = regex
Select a UPS on a specific USB bus or group of busses. The argument
is a regular expression that must match the bus name where the UPS
is connected (e.g. bus="002", bus="00[2-3]").
subdriver = string
Select a serial-over-USB subdriver to use. You have a choice
between cypress, fabula, fuji, ippon, krauler and phoenix. When
using this option, it is mandatory to also specify the vendorid and
productid.
langid_fix = value
Apply the language ID workaround to the krauler subdriver. This is
mandatory for some devices to work (LDLC, Dynamix and others). You
must provide value (0x409 or 0x4095), according to your device
entry in NUT hardware compatibility list (HCL).
IMPLEMENTATION NOTES
fabula subdriver
This subdriver, meant to be used with the megatec protocol,
does not support the various test.battery commands. Plus, the
shutdown.return command ignores the values set in
ups.delay.start/ondelay and makes the UPS turn on the load as
soon as power is back.
fuji subdriver
This subdriver, meant to be used with the megatec protocol,
does not support the shutdown.stayoff and load.off commands.
Plus, the shutdown.return command ignores the values set in
ups.delay.start/ondelay and makes the UPS turn on the load as
soon as power is back.
krauler subdriver
This subdriver, meant to be used with the megatec protocol,
does not support the shutdown commands, i.e.: shutdown.return,
shutdown.stayoff and load.off.
UPS COMMANDS
This driver supports some instant commands (see upscmd(8)):
beeper.toggle
Toggle the UPS beeper. (Not available on some hardware)
load.on
Turn on the load immediately. (Not available on some hardware)
load.off
Turn off the load immediately (see KNOWN PROBLEMS).
shutdown.return
Turn off the load and return when power is back. Uses the timers
defined by ups.delay.start and ups.delay.shutdown.
shutdown.stayoff
Turn off the load and remain off (see KNOWN PROBLEMS). Uses the
timer defined by ups.delay.shutdown.
shutdown.stop
Stop a shutdown in progress.
test.battery.start.deep
Perform a long battery test. (Not available on some hardware)
test.battery.start.quick
Perform a quick (10 second) battery test.
test.battery.stop
Stop a running battery test. (Not available on some hardware)
BESTUPS, MECER, MEGATEC, MEGATEC/OLD, MUSTEK, Q1, ZINTO PROTOCOLS
test.battery.start value
Perform a battery test for the duration of value seconds (truncated
to 60 seconds) [60..5940].
VOLTRONIC POWER P98 UNITS (WITH MECER PROTOCOL)
test.battery.start value
Perform a battery test for the duration of value seconds
(truncated to 60 seconds) [12..5940]. This value is truncated
to units of 6 seconds (less than 60 seconds) or 60 seconds
(more than 60 seconds).
VOLTRONIC PROTOCOL
The following instant commands are available for the voltronic
protocol. Not all of them are available on all the UPSes supported by
this protocol.
beeper.enable
Enable the UPS beeper.
beeper.disable
Disable the UPS beeper.
test.battery.start value
Perform a battery test for the duration of value seconds
[12..5940]. This value is truncated to units of 6 seconds (less
than 60 seconds) or 60 seconds (more than 60 seconds).
outlet.1.load.off
Turn off outlet 1 load immediately.
outlet.1.load.on
Turn on outlet 1 load immediately.
outlet.2.load.off
Turn off outlet 2 load immediately.
outlet.2.load.on
Turn on outlet 2 load immediately.
outlet.3.load.off
Turn off outlet 3 load immediately.
outlet.3.load.on
Turn on outlet 3 load immediately.
outlet.4.load.off
Turn off outlet 4 load immediately.
outlet.4.load.on
Turn on outlet 4 load immediately.
bypass.start
Put the UPS in ECO Mode.
bypass.stop
Take the UPS out of ECO Mode.
BATTERY CHARGE
Due to popular demand, this driver will report a guesstimated
battery.charge and optionally battery.runtime, provided you specified a
couple of the EXTRA ARGUMENTS listed above.
If you specify both battery.voltage.high and battery.voltage.low in
ups.conf(5), but don’t enter runtimecal, it will guesstimate the state
of charge by looking at the battery voltage alone. This is not reliable
under load, as this only gives reasonably accurate readings if you
disconnect the load, let the battery rest for a couple of minutes and
then measure the open cell voltage. This just isn’t practical if the
power went out and the UPS is providing power for your systems.
battery.voltage - battery.voltage.low
battery.charge = ------------------------------------------ x 100 %
battery.voltage.high - battery.voltage.low
There is a way to get better readings without disconnecting the load
but this requires one to keep track on how much (and how fast) current
is going in and out of the battery. If you specified the runtimecal,
the driver will attempt to do this. Note however, that this heavily
relies on the values you enter and that the UPS must be able to report
the load as well. There are quite a couple of devices that report 0 %
(or any other fixed value) at all times, in which case this obviously
doesn’t work.
The driver also has no way of determining the degradation of the
battery capacity over time, so you’ll have to deal with this yourself
(by adjusting the values in runtimecal). Also note that the driver
guesses the initial state of charge based on the battery voltage, so
this may be less than 100 %, even when you are certain that they are
full. There is just no way to reliably measure this between 0 and 100 %
full charge.
This is better than nothing (but not by much). If any of the above
calculations is giving you incorrect readings, you are the one that put
in the values in ups.conf(5), so don’t complain with the author. If you
need something better, buy a UPS that reports battery.charge and
battery.runtime all by itself without the help of a NUT driver.
NOTES FOR THE PREVIOUS USER OF MEGATEC DRIVERS
The nutdrv_qx driver having replaced the megatec ones, some
configuration changes may be required by users switching to nutdrv_qx.
Part of this, the following megatec options, in ups.conf(5), have to be
changed:
battvolts
You need to use default.battery.voltage.high and
default.battery.voltage.low
dtr and rts
You need to use cablepower
ignoreoff
This parameter can simply be discarded, since it was a wrong
understanding of the specification.
NOTES FOR THE PREVIOUS USER OF BLAZER DRIVERS
The nutdrv_qx driver having replaced the blazer ones, some
configuration changes may be required by users switching to nutdrv_qx.
Part of this, the following blazer options, in ups.conf(5), have to be
changed:
ondelay
While the previous blazer drivers expected minutes, the new
nutdrv_qx driver wants seconds.
The following instant command has also been changed:
test.battery.start value
While the old blazer drivers expected a value in minutes, the
nutdrv_qx driver wants a value in seconds.
NOTES FOR THE PREVIOUS USER OF BESTUPS DRIVER
The nutdrv_qx driver having replaced the bestups one, some
configuration changes may be required by users switching to nutdrv_qx.
Part of this, the following bestups options, in ups.conf(5), are no
longer supported by this driver:
nombattvolt, battvoltmult
See BATTERY CHARGE.
ID
Discarded.
NOTES FOR THE PREVIOUS USER OF VOLTRONIC DRIVERS
The nutdrv_qx driver having replaced the voltronic ones, some
configuration changes may be required by users switching to nutdrv_qx.
Part of this, the following voltronic options, in ups.conf(5), have to
be changed:
ondelay
While the previous voltronic drivers expected minutes, the new
nutdrv_qx driver wants seconds. It no longer defaults to 0 minutes
but to 3 minutes (i.e. 180 seconds) for compatibility with the
users switching from the old blazer drivers.
battnumb
This option has been renamed to battery_number.
The following options are no longer supported by this driver, you can
now change them more conveniently ‘on the fly’ calling upsrw(8) with
the appropriate NUT variable - provided that your UPS supports them.
battpacks → battery.packs
Set number of battery
packs in parallel [1..99].
This setting will change
the charge and runtime
estimation reported by the
UPS.
battlow → battery.voltage.low
Set minimum battery
voltage just before the
UPS automatically shuts
down. This setting will
change the charge and
runtime estimation
reported by the UPS.
auto_reboot → ups.start.auto
Enable or disable auto
reboot [enabled/disabled].
If enabled, the UPS will
auto recover when AC power
returns.
battery_protection → battery.protection
Enable or disable battery
deep discharge protection
[enabled/disabled].
energy_saving → battery.energysave
Enable or disable Green
power function
[enabled/disabled]. If
enabled, for energy
saving, the UPS will auto
off when there is no load.
cold_start → ups.start.battery
Enable or disable Cold
Start [enabled/disabled].
If enabled, the UPS can be
turned on also if AC is
not connected to the UPS.
outlet_control → outlet.0.switchable
Enable or disable
programmable outlets
control at battery mode
[enabled/disabled]. If
enabled, the UPS will cut
off programmable outlets
after backup time (set
through
outlet.{1,2,3,4}.delay.shutdown)
arrives. If disabled, the
UPS will provide
continuous power to
programmable outlets until
the battery is running
out.
max_eco_volt → input.transfer.high
Maximum voltage for ECO Mode
(V). If AC voltage is within
acceptable range, ECO mode will
be used (If the UPS is capable
of and it’s enabled).
min_eco_volt → input.transfer.low
Minimum voltage for ECO Mode
(V). If AC voltage is within
acceptable range, ECO mode will
be used (If the UPS is capable
of and it’s enabled).
max_eco_freq → input.frequency.high
Maximum frequency for ECO Mode
(Hz). If AC frequency is within
acceptable range, ECO mode will
be used (If the UPS is capable
of and it’s enabled).
min_eco_freq → input.frequency.low
Minimum frequency for ECO Mode
(Hz). If AC frequency is within
acceptable range, ECO mode will
be used (If the UPS is capable
of and it’s enabled).
outlet1_delay → outlet.1.delay.shutdown
Delay time before programmable
outlet 1 shuts down the load
when on battery mode [0..59940]
(seconds).
outlet2_delay → outlet.2.delay.shutdown
Delay time before programmable
outlet 2 shuts down the load
when on battery mode [0..59940]
(seconds).
outlet3_delay → outlet.3.delay.shutdown
Delay time before programmable
outlet 3 shuts down the load
when on battery mode [0..59940]
(seconds).
outlet4_delay → outlet.4.delay.shutdown
Delay time before programmable
outlet 4 shuts down the load
when on battery mode [0..59940]
(seconds).
batt_type → battery.type
Battery type (for P31 UPSes
only) [Li/Flooded/AGM].
KNOWN PROBLEMS
Some UPS commands aren’t supported by all models. In most cases, the
driver will send a message to the system log when the user tries to
execute an unsupported command. Unfortunately, some models don’t even
provide a way for the driver to check for this, so the unsupported
commands will silently fail.
Both the load.off and shutdown.stayoff instant commands are meant to
turn the load off indefinitely. However, some UPS models don’t allow
this.
Some models report a bogus value for the beeper status (will always be
enabled or disabled). So, the beeper.toggle command may appear to have
no effect in the status reported by the driver when, in fact, it is
working fine.
The temperature and load value is known to be bogus in some models.
VOLTRONIC-QS UNITS
Both load.off and shutdown.stayoff instant commands are known to work
as expected (i.e. turn the load off indefinitely) only if mains is
present, otherwise, as soon as mains returns the load will be powered.
After issuing a shutdown.return instant command, the UPS won’t wait
ondelay before powering on the load, provided the following conditions
are met:
· if the load has been previously (no matter how long before) powered
off through load.off/shutdown.stayoffand powered on through
load.on/shutdown.stopand
· if AC wasn’t cut after issuing the load.off/shutdown.stayoff (i.e.
the UPS didn’t turn itself off) and
· if there’s a power outage after issuing the shutdown.return command
In this case, as soon as mains returns the load will be powered.
VOLTRONIC-QS-HEX UNITS
shutdown.return, load.off, and shutdown.stayoff instant commands are
known to work as expected only if mains is present, otherwise, as soon
as mains returns the load will be powered.
UPS WARNINGS (VOLTRONIC PROTOCOL)
The UPSes supported by voltronic protocol report warnings through a
64bit flag (bit1bit2...bit63bit64) where 1 means that a warning arose,
while 0 means no warning. Since more than one warning at a time can be
signaled, and because of the limited space in the ups.alarm variable,
if the length of the warnings exceeds that of ups.alarms variable, they
will be reported as bits. If you want to know the explanation of that
bit you can either watch the log or see the next table (unlisted bits
equal to unknown warnings).
Table 1. UPS Warnings for voltronic UPSes
┌───┬────────────────────────────┐
│ # │ Corresponding Warning │
├───┼────────────────────────────┤
│ │ │
│ 1 │ Battery disconnected │
├───┼────────────────────────────┤
│ │ │
│ 2 │ Neutral not connected │
├───┼────────────────────────────┤
│ │ │
│ 3 │ Site fault │
├───┼────────────────────────────┤
│ │ │
│ 4 │ Phase sequence incorrect │
├───┼────────────────────────────┤
│ │ │
│ 5 │ Phase sequence incorrect │
│ │ in bypass │
├───┼────────────────────────────┤
│ │ │
│ 6 │ Input frequency unstable │
│ │ in bypass │
├───┼────────────────────────────┤
│ │ │
│ 7 │ Battery overcharged │
├───┼────────────────────────────┤
│ │ │
│ 8 │ Low battery │
├───┼────────────────────────────┤
│ │ │
│ 9 │ Overload alarm │
├───┼────────────────────────────┤
│ │ │
│10 │ Fan alarm │
├───┼────────────────────────────┤
│ │ │
│11 │ EPO enabled │
├───┼────────────────────────────┤
│ │ │
│12 │ Unable to turn on UPS │
├───┼────────────────────────────┤
│ │ │
│13 │ Over temperature alarm │
├───┼────────────────────────────┤
│ │ │
│14 │ Charger alarm │
├───┼────────────────────────────┤
│ │ │
│15 │ Remote auto shutdown │
├───┼────────────────────────────┤
│ │ │
│16 │ L1 input fuse not working │
├───┼────────────────────────────┤
│ │ │
│17 │ L2 input fuse not working │
├───┼────────────────────────────┤
│ │ │
│18 │ L3 input fuse not working │
├───┼────────────────────────────┤
│ │ │
│19 │ Positive PFC abnormal in │
│ │ L1 │
├───┼────────────────────────────┤
│ │ │
│20 │ Negative PFC abnormal in │
│ │ L1 │
├───┼────────────────────────────┤
│ │ │
│21 │ Positive PFC abnormal in │
│ │ L2 │
├───┼────────────────────────────┤
│ │ │
│22 │ Negative PFC abnormal in │
│ │ L2 │
├───┼────────────────────────────┤
│ │ │
│23 │ Positive PFC abnormal in │
│ │ L3 │
├───┼────────────────────────────┤
│ │ │
│24 │ Negative PFC abnormal in │
│ │ L3 │
├───┼────────────────────────────┤
│ │ │
│25 │ Abnormal in CAN-bus │
│ │ communication │
├───┼────────────────────────────┤
│ │ │
│26 │ Abnormal in synchronous │
│ │ signal circuit │
├───┼────────────────────────────┤
│ │ │
│27 │ Abnormal in synchronous │
│ │ pulse signal circuit │
├───┼────────────────────────────┤
│ │ │
│28 │ Abnormal in host signal │
│ │ circuit │
├───┼────────────────────────────┤
│ │ │
│29 │ Male connector of parallel │
│ │ cable not connected well │
├───┼────────────────────────────┤
│ │ │
│30 │ Female connector of │
│ │ parallel cable not │
│ │ connected well │
├───┼────────────────────────────┤
│ │ │
│31 │ Parallel cable not │
│ │ connected well │
├───┼────────────────────────────┤
│ │ │
│32 │ Battery connection not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│33 │ AC connection not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│34 │ Bypass connection not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│35 │ UPS model types not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│36 │ Capacity of UPSs not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│37 │ Auto restart setting not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│38 │ Battery cell over charge │
├───┼────────────────────────────┤
│ │ │
│39 │ Battery protection setting │
│ │ not consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│40 │ Battery detection setting │
│ │ not consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│41 │ Bypass not allowed setting │
│ │ not consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│42 │ Converter setting not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│43 │ High loss point for │
│ │ frequency in bypass mode │
│ │ not consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│44 │ Low loss point for │
│ │ frequency in bypass mode │
│ │ not consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│45 │ High loss point for │
│ │ voltage in bypass mode not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│46 │ Low loss point for voltage │
│ │ in bypass mode not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│47 │ High loss point for │
│ │ frequency in AC mode not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│48 │ Low loss point for │
│ │ frequency in AC mode not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│49 │ High loss point for │
│ │ voltage in AC mode not │
│ │ consistent in parallel │
│ │ systems │
├───┼────────────────────────────┤
│ │ │
│50 │ Low loss point for voltage │
│ │ in AC mode not consistent │
│ │ in parallel systems │
├───┼────────────────────────────┤
│ │ │
│51 │ Warning for locking in │
│ │ bypass mode after 3 │
│ │ consecutive overloads │
│ │ within 30 min │
├───┼────────────────────────────┤
│ │ │
│52 │ Warning for three-phase AC │
│ │ input current unbalance │
├───┼────────────────────────────┤
│ │ │
│53 │ Warning for a three-phase │
│ │ input current unbalance │
│ │ detected in battery mode │
├───┼────────────────────────────┤
│ │ │
│54 │ Warning for Inverter │
│ │ inter-current unbalance │
├───┼────────────────────────────┤
│ │ │
│55 │ Programmable outlets cut │
│ │ off pre-alarm │
├───┼────────────────────────────┤
│ │ │
│56 │ Warning for Battery │
│ │ replace │
├───┼────────────────────────────┤
│ │ │
│57 │ Abnormal warning on input │
│ │ phase angle │
├───┼────────────────────────────┤
│ │ │
│58 │ Warning!! Cover of │
│ │ maintain switch is open │
├───┼────────────────────────────┤
│ │ │
│62 │ EEPROM operation error │
└───┴────────────────────────────┘
AUTHORS
Daniele Pezzini <hyouko@gmail.com>, Arnaud Quette
<arnaud.quette@gmail.com>, John Stamp <kinsayder@hotmail.com>, Peter
Selinger <selinger@users.sourceforge.net>, Arjen de Korte
<adkorte-guest@alioth.debian.org>, Alexander Gordeev
<lasaine@lvk.cs.msu.su>
SEE ALSOblazer_ser(8), blazer_usb(8), nutupsdrv(8), ups.conf(5), upsc(8),
upscmd(8), upsdrvctl(8), upsmon(8), upsrw(8)
Internet Resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
The NUT HCL: http://www.networkupstools.org/stable-hcl.html
Network UPS Tools 2.7.3 04/22/2015 NUTDRV_QX(8)