CLONE(8)		    Network UPS Tools (NUT)		      CLONE(8)

NAME
       clone - UPS driver clone

NOTE
       This man page only documents the specific features of the clone driver.
       For information about the core driver, see nutupsdrv(8).

DESCRIPTION
       This driver, which sits on top of  another  driver  socket,  allows  to
       group  clients  to  a  particular outlet of a device and deal with this
       output as if it was a normal UPS.

EXTRA ARGUMENTS
       This driver supports the following settings:

       load.off=command
	      Recommended.  Set the command on the 'real' UPS driver that will
	      be  used	to  switch off the outlet.  You need both load.off and
	      load.on in order to power cycle the outlet.  Otherwise, shutting
	      down  the	 clients powered by an outlet is a one way street (see
	      IMPORTANT).

       load.on=command
	      Recommended.  Set the command on the 'real' UPS driver that will
	      be  used	to  switch  on the outlet.  You need both load.off and
	      load.on in order to power cycle the outlet.  Otherwise, shutting
	      down  the	 clients powered by an outlet is a one way street (see
	      IMPORTANT).

       load.status=value
	      Recommended.  Set the variable on the  'real'  UPS  driver  that
	      will  be used to indicate the outlet status (ie on/off).	If not
	      specified, the clone driver will attempt to keep	track  of  the
	      outlet status, but this is less reliable.

       offdelay=num
	      Set the timer (in seconds) before the outlet is turned off after
	      the shutdown condition (OB LB) for this outlet is met or a  com‐
	      mand to shutdown was issued.  Defaults to 120 seconds.

       ondelay=num
	      Set  the	timer (in seconds) for the outlet to switch on in case
	      the power	 returns  after	 the  oulet  has  been	switched  off.
	      Defaults to 30 seconds.

       mincharge=value
	      Set  the	remaining battery level when the clone UPS switches to
	      LB (percent).

       minruntime=value
	      Set the remaining battery runtime when the clone UPS switches to
	      LB (seconds).

IMPLEMENTATION
       The  port  specification in the ups.conf(5) reference the driver socket
       that the 'real' UPS driver is using. For example:

       [realups]
	  driver = usbhid-ups
	  port = auto

       [clone-outlet-1]
	  driver = clone
	  port = usbhid-ups-realups
	  load.on = outlet.1.load.on
	  load.off = outlet.1.load.off
	  load.status = outlet.1.status
	  [...]

IMPORTANT
       Unlike a real UPS, you should not configure a upsmon  master  for  this
       driver.	 When  a upsmon master sees the OB LB flags and tells the upsd
       server it is OK to initiate the	shutdown  sequence,  the  server  will
       latch the FSD status and it will not be possible to restart the systems
       connected without restarting the upsd server.

       This will be a problem if the power returns after the clone UPS	initi‐
       ated  the shutdown sequence on it's outlet, but returns before the real
       UPS begins shutting down. The solution is in  the  clone	 driver,  that
       will insert the FSD flag if needed without the help of a upsmon master.

CAVEATS
       The  clone  UPS will follow the status on the real UPS driver.  You can
       only make the clone UPS shutdown earlier than the real UPS driver,  not
       later.	If  the	 real  UPS  driver initiates a shutdown, the clone UPS
       driver will immediately follow.

       Be aware that the commands to shutdown/restart an outlet	 on  the  real
       UPS  drivers  are  not  affected, so if you tell the real UPS driver to
       shutdown the outlet of the clone UPS driver,  your  clients  will  lose
       power without warning.

AUTHOR
       Arjen de Korte <adkorte-guest@alioth.debian.org>

SEE ALSO
       upscmd(1), upsrw(1), ups.conf(5), nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

				Mon Jul 20 2009			      CLONE(8)
[top]

List of man pages available for Mandriva

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net